Using old CANIO with MC405/MC403

Using old CANIO with MC405/MC403

The P315//P316 and P319 all use the same Canbus protocol. The only thing we have seen with the old modules connected to the new MC4xx is that they do not power up fast enough so the MC405 must be programmed to wait a few seconds then start the Canbus.
    • Related Articles

    • Could not restart CANIO with CANIO_STATUS

      CAN IO modules went into error and could not be reset by CANIO_STATUS.4 = 1. After some tests, the customer found the issue was as follows: It was solved by providing isolation for Trio and Can IO module from the panel. Also used separate 24V supply ...
    • MC_CONFIG vs Flash parameters

      All Motion Coordinators store the IP_ADDRESS, IP_NETMASK and IP_GATEWAY in Flash memory.  So there is usually no need to add them to the MC_CONFIG. There are some differences with other system parameters. MC4N-ECAT, MC4N-RTX, MC6N-ECAT, Flex-6 Nano ...
    • CANbus port check

      MC403, MC405, Euro404 and Euro408 Motion Coordinators that appear to have a failed CANbus port. Check that the CANIO_ADDRESS is set to 32 when using Trio CANIO mode or to 40 .. 42 when using CanOpen. The CANIO_ADDRESS is stored in Flash in the above ...
    • CAN IO Address Problem

      The Leds on the module are a binary code. LEDs 8, 9 and 10 ON woud be code 7 = System Shutdown. Usually this is caused by interference on the CAN lines. Check the correct screened cable has been used and that both ends are terminated with 120 Ohm ...
    • Replace EURO205X with EURO209

      The Euro 209 and Euro 404/408 share the same pinout arrangement which is somewhat different to the Euro 205(x). So changing from 205 to either the 404 or 408 will have the same hardware challenges. Software wise the 205/404 difference is similar to ...