Could not restart CANIO with CANIO_STATUS

Could not restart CANIO with CANIO_STATUS

CAN IO modules went into error and could not be reset by CANIO_STATUS.4 = 1. After some tests, the customer found the issue was as follows:

It was solved by providing isolation for Trio and Can IO module from the panel.
Also used separate 24V supply for Trio can and IO module supply .
The panel earthing was the issue, despite the voltage difference was less than 3V.

This issue was a rare one faced for this OEM as they have more than 100+ Trio machines running without a problem.
    • Related Articles

    • AN-316 CANOpen IO Setup Guide

      There are 2 modes of CAN operation available: 1. Trio CANbus protocol. This is the default protocol and is tailored for the high performance Input/Output needed in a Motion System. 2. CanOpen to Can in Automation standards CiA301 and CiA401. Option 2 ...
    • How to pause and restart a BASIC program

      BASIC programs run best when left to run continuously with functions controlled by setting values in the global VR varables. However sometimes it is necessary to put a program in a "paused" state while another program takes control of something. The ...
    • DRIVE_STATUS issue (EtherCAT CoE status word)

      DRIVE_STATUS is the value of the CoE status word. Object number 0x6041. If bit 11 is set in the status in the drive then we must see the same in DRIVE_STATUS. If not then the drive is not setting the bit in Object 0x6041. You can check the object ...
    • CAN IO Address Problem

      The Leds on the module are a binary code. LEDs 8, 9 and 10 ON woud be code 7 = System Shutdown. Usually this is caused by interference on the CAN lines. Check the correct screened cable has been used and that both ends are terminated with 120 Ohm ...
    • Axis Status Error

      Just picked up my Flex-6 Nano again to do some testing with movelink, for some reason my FLEX-3AX is throwing errors. pressing the error reset button is not changing anything. All 3 axis are the same: Answer: The Fault bit in the CoE status will be ...