CANbus port check

CANbus port check

MC403, MC405, Euro404 and Euro408 Motion Coordinators that appear to have a failed CANbus port.

Check that the CANIO_ADDRESS is set to 32 when using Trio CANIO mode or to 40 .. 42 when using CanOpen. The CANIO_ADDRESS is stored in Flash in the above Motion Coordinators so will remember the setting even if removed from the MC_CONFIG. Check in the Motion Perfect terminal #0 by typing PRINT CANIO_ADDRESS.

>>PRINT CANIO_ADDRESS
32
>>
    • Related Articles

    • CAN IO Address Problem

      The Leds on the module are a binary code. LEDs 8, 9 and 10 ON woud be code 7 = System Shutdown. Usually this is caused by interference on the CAN lines. Check the correct screened cable has been used and that both ends are terminated with 120 Ohm ...
    • Could not restart CANIO with CANIO_STATUS

      CAN IO modules went into error and could not be reset by CANIO_STATUS.4 = 1. After some tests, the customer found the issue was as follows: It was solved by providing isolation for Trio and Can IO module from the panel. Also used separate 24V supply ...
    • AN-316 CANOpen IO Setup Guide

      There are 2 modes of CAN operation available: 1. Trio CANbus protocol. This is the default protocol and is tailored for the high performance Input/Output needed in a Motion System. 2. CanOpen to Can in Automation standards CiA301 and CiA401. Option 2 ...
    • Changing EtherCAT drive address

      There are 3 methods to set the address in the servo-drive; 1 . If there are rotary address switches on the front of the drive, then they may be used to select the address. 2. The address may be set in memory, either via a front panel keypad or ...
    • Modbus TCP and Ethernet IP on Flex-6-Nano

      Q. Can we run and use Modbus TCP server and Ethernet IP server on Flex-6-Nano at the same time? A. Yes you can use both in parallel. They open different "port" numbers on the Ethernet communications but have the same IP Address. For example Modbus is ...