Hardware
What are the recommended external fuse ratings for Trio products?
Please see the table below. Product Code Product Name Recommended Main Power External Fuse Recommended IO Power External Fuse P821 MC403-Z 500mA 1A P823 MC403 500mA 1A P826 MC405 500mA 1A P848 MC508 1A 5A + 4A P862 MC664-X 1.2A 1A P900 MC4N-ECAT ...
Flexslice 24V digital input levels
The P372 PNP 16 x Digital Input module has input threshold values to work with standard PLC IO systems. If the input is below 5V then the input is OFF. If the input is above 15V then the input will register as ON.
SD Card Size & Free Space Check
Additional FILE commands for Trio Controllers with Firmware v2.0306 onwards will allow for checks to be made of the size and free space on the SD card fitted into the controller. The two new commands are: FILE "DISK_SIZE" FILE "DISK_FREE" Example ...
How many Flexslice modules can I fit to the P366 coupler?
The EBUS power source from the coupler and Flex-6 Nano at 40 degrees celcius are: P600 : 2700 mA maximum. P366 : 2860 mA maximum. The maximum number of modules is defined by the power on the EBUS and the propagation times over the EBUS data ...
MC403 encoder power overload
Issue: The 5 volt supply is taken from an axis port of the MC403 and cable length is >15 meters. After 15-20 days the power supply overloaded alarms comes. After removing and reconnecting the cable, the alarm went away. But after 2-3 days alarm came ...