Kollmorgen drive with SERVO_PERIOD issue

Kollmorgen drive with SERVO_PERIOD issue

EtherCAT network goes in operational state only with SERVO_PERIOD=250 µsec setting when Kollmorgen drives are in use. The network stays in safe-operational state with any other servo period setting.

The following needs to be done;

* MC_CONFIG to be modified for each axis.

      SERVO_PERIOD = 1000
      NODE_SYNC_OFFSET(0,0)=560000

* The EC_EXTEND file -> ESC configurations page -> Size to be 128
    • Related Articles

    • EURO 404 - Motion Problem at SERVO_PERIOD 250

      A motion problem could occur when running MC403, MC405, Euro404 or Euro408 at 250 usec servo period. The moves would stop (buffers frozen) and an uncommanded movment could occur on one axis in an XY pair. The issue occured very infrequently and was ...
    • What does SERVO_OFFSET do?

      SERVO_OFFSET is a system parameter that is usually set by the operating system.  The value depends on the SERVO_PERIOD, the modules fitted (to a MC664X) and the model of Motion Coordinator.  It should not be necessary to set this in a system.  Only ...
    • Changing EtherCAT drive address

      There are 3 methods to set the address in the servo-drive; 1 . If there are rotary address switches on the front of the drive, then they may be used to select the address. 2. The address may be set in memory, either via a front panel keypad or ...
    • AN-315 EtherCAT setup for Panasonic A5B Drive

      The recommendations within this document applies to the Trio MC464+P876 EtherCAT master and the Trio MC4N-ECAT EtherCAT Master used with the Panasonic Minas A5B EtherCAT servo drive. When delivered, the Panasonic A5B has 2 features set; the Positive ...
    • DRIVE_STATUS issue (EtherCAT CoE status word)

      DRIVE_STATUS is the value of the CoE status word. Object number 0x6041. If bit 11 is set in the status in the drive then we must see the same in DRIVE_STATUS. If not then the drive is not setting the bit in Object 0x6041. You can check the object ...