Following error

Following error

We have a customer with a MC664x that has an issue with FE in a master axis.
The machine is a printer and the axis is a rotary axis controlled by speed.
The FE_LIMIT is configured at maximum value (4.0e17).
He sends a video where we can see how FE is increasing to great values until the controller collapses and is not possible to stop, motor runs without control, and only the emergency stops are effective.

He uses a "FORWARD" function to move the axis.

It seems that some concepts are wrong in configuration mode but I don't know what.

Answer:
We could see DPOS moveing + and MPOS moving -. suggest that they have the encoder connected the wrong way around. MPOS must be counting the same way as DPOS.
    • Related Articles

    • Following error when using CSP in M753 Control Techniques drives

      Target Position is in DAC_OUT in CSP mode Encoder position is in ENCODER in CSP mode. Both can be monitored on the scope. FE is DPOS - MPOS so has a larger value than the real following error due to the EtherCAT cycle time. Set FE_LIMIT to suit the ...
    • Question -following error

      Check FE_LIMIT and DRIVE_FE_LIMIT are set to sensible values. You could watch FE and DRIVE_FE (assuming the Actual Following Error is in the PDO) in the Motion Perfect Scope to see if the change in following error is proportional to speed.
    • Trio Motion Coordinator MC403 sudden axis status error

      Q: We always come up with “Axis Status: Error” and the active status flag is W (1) – Following error warning range and motor stops nearly instantly with E (8) – Following error exceeds limit.  How can we solve it? A: With SERVO=OFF, can you make the ...
    • Jitter on the direction output, MC403-Z P821

      When using a MC403-Z P821, we are facing with an issue related to the "direction" signal. Please take a look at the following picture: Scope screen We have connected the oscilloscope on the step signal (channel 1) and direction signal (channel 2). ...
    • P375 card with 3 stepper - MPOS and DPOS in error

      Even with open loop stepper, the P375 has an encoder counter that counts the pulses and sends them back to the controller so that we can do registration. The feedback is in pulse counts but DPOS is in counts x 256. Therefore it is necessary to set ...