Flex Nano not connecting to EtherCAT or HMI (E09 Error)

Flex Nano not connecting to EtherCAT or HMI (E09 Error)

Please confirm that the firmware has been upgraded to 2.0318 or later with Bootloader V2.05 according to the technical bulletin.  TB2202_Flex-6 and MC6N update.

The Bulletin was distributed on 9th December 2022.

After installing the update, the old 2.0315 can be re-installed and the Flex-6 will keep the new bootloader V2.05.  This will solve the E09 problem.
    • Related Articles

    • Rolling back firmware on Flex-6 Nano

      Q. Since we’ve updated to v2.0322 there have been issues noticed on our rigs and immediately they are wondering if the TRIO firmware update might be to blame as nothing else changed. Is it possible to roll back the TRIO firmware from v2.0322 to ...
    • Axis Status Error

      Just picked up my Flex-6 Nano again to do some testing with movelink, for some reason my FLEX-3AX is throwing errors. pressing the error reset button is not changing anything. All 3 axis are the same: Answer: The Fault bit in the CoE status will be ...
    • AN-399 TrioPC Motion Performance with Flex-6 Nano

      This document describes some timing tests with made with TrioPC motion Active X and Flex-6 Nano Motion Coordinator.
    • General EtherCAT Error

      Motion Coordinator reports a General EtherCAT Error with a number.  What does it mean? Error - General Ethercat Error(8) = invalid data, exceeded maximum telegram length (by attempting  to add too much data into the telegram.) Error - General ...
    • Question about Omron R88D and Trio Firmware 2.0296

      The most likely issue is that the R88D cannot use the Trio as clock master in that Trio firmware version. You must add this command to force the first drive to be Distributed Clocks Master. Set the first drive with DC capability to be the Distributed ...