AN-411 CAN P329 Intro Guide
Trio CAN 16-IN 16-OUT modules allow I/O expansion for the CAN enabled Trio Motion Coordinators. The P329 module fits in the existing Trio CAN range, providing a single module with 16 digital inputs and 16 digital outputs.
This document describes explains how to use the P329 CAN IO expansion module
Inputs
Input channels are opto-isolated 24V, which are designed to be ON when the input voltage is greater than 18 Volts and OFF when the signal voltage is below 2V. The input has a 6k8 resistor in series and so provides a load of approximately 3.5mA at 24V.
Outputs
Output channels have a protected 24V sourcing output connected to the output pin. The output circuit has electronic over-current protection and thermal protection which shuts the output down when the current exceeds 250mA.
Care should be taken to ensure that the 250mA limit for the output circuit is not exceeded, and that the total load for the group of 8 outputs does not exceed 1 amp.
With no load, the outputs may 'float' up to 24V even when off. Fit a load resistor, for example 10k, when bench testing the outputs of the P329.
Related Articles
Flexslice Loading/Configuration Limits - EBUS Load
EBUS loading of the the Flex-6 Nano and the Flex Coupler (P366) is limited to 16. Attached is a spreadsheet to calculate your projects requirements and highlight any possible limitations.
virtual output
Q: How do I used a virtual output? How can I read the state of the virtual output? A: Set virtual output with OP. Read virtual output with IN. OP(24,ON) IF IN(24)=ON THEN PRINT "OK" ENDIF
Flexslice 24V digital input levels
The P372 PNP 16 x Digital Input module has input threshold values to work with standard PLC IO systems. If the input is below 5V then the input is OFF. If the input is above 15V then the input will register as ON.
AN-316 CANOpen IO Setup Guide
There are 2 modes of CAN operation available: 1. Trio CANbus protocol. This is the default protocol and is tailored for the high performance Input/Output needed in a Motion System. 2. CanOpen to Can in Automation standards CiA301 and CiA401. Option 2 ...
Registration input to step output delay
REGIST will precisely capture a position within microsconds but the MARK goes TRUE only on the following servo cycle, so as a raw edge detection it is no faster than an IN command. The only advantage is that you get to trigger on an edge with REGIST. ...