AN-356 Firmware update procedure for UNIPLAY HMI

AN-356 Firmware update procedure for UNIPLAY HMI

Uniplay 10' (P844) Human Machine Interface may be returned to us with corruption of the Flash that either causes the system to halt or prevents booting altogether.

It is also possible if an update has not been interrupted or was not successful that the Flash can be left without a valid bootloader. In such case this procedure will re-install the OS from an SD Card.

This procedure is valid for 10” models purchased from our supplier after October 2015

    • Related Articles

    • AN-412 Replacing firmware on UNIPLAY-7 MK1

      The HMI firmware 1.29 and above does not work with UNIPLAY-7 Mk1* If in case, there was an update made to these UNIPLAY-7 Mk1*, the HMI client does not boot anymore. In this document describes how to restore the firmware back to the original * :- How ...
    • AN-343 Jogging axis with Trio UNIPLAY HMI

      This document will show the user some tips to program a jogging operation with a Trio Uniplay HMI.
    • Uniplay HMI IP Address Change Using Motion Perfect

      A video is available on our Trio Website showing how to carry out the IP address of your Uniplay 7 or 10 HMI. Please follow this link. http://www.triomotion.uk/system/downloadPage.php?location=%2Fvideos%2FUniplay_HMI
    • AN-325 Use DTP7-W Pendant with Uniplay

      Use a DTP7-W DAINCUBE pendant with Uniplay and communicate with Trio controllers.
    • AN-429 Replacing Lithium battery on UNIPLAY HMI

      The UNIPLAY HMI takes one CR2032 / CR1225 / CR1220 coin lithium battery to keep the RTC running. Battery specification: CR2032 / CR1225 / CR1220 3V lithium battery. This document explains how to change this battery